uirements
Result
Lightning
protection
The grounding cable of the chassis is well
grounded.
The grounding terminal of the AC power
receptacle is well grounded.
A power lightning arrester is installed. (Optional)
Electricity safety
Equip an uninterrupted power supply (UPS).
In case of emergency during operation, switch off
the external power switch.
Rack-mounting
requirements
The front and rear of the rack are at least 1 m
(3.28 ft) away from walls or other devices.
The equipment room is at least 3 m (9.84 ft) high
and an air conditioner is installed.
Tools
Installation accessories supplied with the L1000-A
User supplied tools
Reference
Documents shipped with the L1000-A
Online documents